ac dc din rail power supply
Welcome friends all over the world , let us develop mutual co-operation to achieve a win-win.
SPECIFICATIONS |
OUTPUT | |
Model | DR-240-24 | DR-240-48 |
DC Voltage | 24V | 48V |
Rated Current | 10A | 5A |
Current Range | 0-10A | 0-5A |
Rated Power | 240W | 240W |
Ripple & Noise | 80mVp-p | 150mVp-p |
Voltage Adj. Range | 24-28V | 48-53V |
Voltage Tolerance | ±1% | ±1% |
Setup, Rise Time | 800ms,40ms/230VAC 800ms,40ms/115VAC at full load |
Hold Up Time | 24ms/230VAC 24ms/115VAC at full load |
| |
INPUT | |
Voltage Range | 85~264VAC 47~63Hz; 120~370VDC |
AC Current | 2.8A/115V 1.4A/230V |
Efficiency | 84% | 85% |
Inrush Current | Cold start 27A/115V 45A/230V |
Leakage Current | <3.5mA/240VAC |
| |
PROTECTION | |
Over Load | 105%~150% |
Protection type: Constant current limiting, recovers automatically after fault condition is removed |
Over Voltage | 30-36V | 54-60V |
Protection type: Shut down o/p voltage, re-power on to recover |
Over Temp. | 100°C±5°C(TSW1) |
Protection type: Shut down o/p voltage, recovers automatically after temperature goes down |
| |
ENVIRONMENT | |
Working Temp., Humidity | -10°C~+70°C; 20%~90%RH |
Storage Temp., Humidity | -20°C~+85°C; 10%~95%RH |
Vibration | 10~500Hz, 2G 10min./1cycle, period for 60min, each along X, Y, Z axes |
| |
SAFETY | |
Withstand Voltage | I/P-O/P: 3KVAC I/P-FG: 1.5KVAC O/P-FG: 0.5KVAC |
Isolation Resistance | I/P-O/P, I/P-FG, O/P-FG: 100M Ohms / 500VDC |
| |
STANDARD | |
Safety Standard | Design refer to UL508,UL60950-1, TUV EN60950-1 |
EMC Standard | EN55011,EN55022,EN61000-3-2,-3,EN61000-4-2,3,4,5,6,8,11,ENV50204,EN55024,EN61000-6-2(EN50082-2) |
| |
OTHERS | |
Dimension | 125.5*125.2*100mm(L*W*H) |
Weight | 1.2Kg |
Packing | 12pcs/15.5Kg/1.2CUFT |
| |
| |